GETTINGSTARTED(continued) StepFour
o ALARM – Alarm operation allows for a single set point (Relay ON and OFF at the same level).
Choose between HIGH and LOW operation.Both operations will require a single set point and a
settingfortheHysteresis(HYSTER)
HIGH–usedtocontrolaHighLevelalarm.Relaywillenergize(ON)whenthelevelisabove
thesettingandwillde‐energize(OFF)whenthelevelfallsbelowthesettingplusthe added
distancefromthehysteresis(HYSTER).
LOW–usedtocontrolaLowLevelalarm.Relaywillenergize(ON)whenthelevelisbelow
thesettingandwillde‐energize(OFF)whenthelevelrisesabovethesettingplustheadded
distancefromthehysteresis(HYSTER).
HYSTER–UsedtoreducechatterbycreatingahysteresisordifferentialfortheAlarmsetpoint.
TheHYST ERvaluewilladj usttheOFFpositionoftheAlarmsettingbytheHYSTERvalue.
SAFE–Eachrelaycan beindividuallyconfiguredtoitsownfail‐safesetting.ChoosebetweenON,OFForHOLD.
o ON–Energizestherelaywhenafail‐safeconditionoccurs
o OFF–De‐energizestherelaywhenafail‐safeconditionoccurs
o HOLD–Keepstherelayinitscurrentstatewhenafail‐safeconditionoccurs
o OUTPUT–Setsthe4/20mAoutputstatewhentheechoislost.Theoptionsare4mA,21mAand
holdlastvalue.
M‐PLEX – when two or three relays are configured as pumps, they can be inter–connected to alternate
betweeneachcycle.
o M‐PLEXisonlyavailablewhen2ormorerelaysaresetforpumps.
o M‐PLEX will not appear when only 1 relay is set for a pump or when the relay functions do not
match(ex:Relay1setforafillingpumpandRelay2setforanemptyingpump).
o SelectingNO‐ALTwillturnOFFtheM‐PLEX.
HELP–Providessetupinformation,theabilitytoresettheEchoSwitch®andasimulationmodetotestthe
relayfunction
o SETUP–WilldisplaythesettingforallfunctionsofEchoSwitch®
o RESET–WillresettheEchoSwitch®backtoitsoriginalfactorysetting
o SIM‐T–SIM(ulation) ‐T(est) willallowtheendusertosimulatechangestoleveltoverifytherelay
settings.UsingtheUPandDOWNbuttonswillincrease
o
TEST P – This is a production test feature used by the factory to confirm operation.This mode
shouldonlybeusedwhensupervisedbyaFlowlinerepres entative.
RUN–Returnstheunittonormalmeasurementandcontrolmode