RevA MN300282 31of34
APPENDIX(continued) StepEight
Simulation (SIM‐T):This mode enables theend user to simulate change s in level without having the level of
liquidmove.ThedisplaywillsimulatelevelofliquidandwillturntherelaysONandOFFaccordingtohowthey
wereconfigured.Example:IfRelay1issetasaHighAlarmwithanONsettingfor100.0inchesandaHysteresis
of2.0 inches,thenwhenthedisplaygoesabove100.0,Relay1willenergizeandwhenthelevelfallsbelow98.0,
Relay1willde‐energize.Usethisfunctiontotestthewiringandtoverifythesensor’sconfiguration.
Please note: Simulation mode will energize and de‐energize all configured relays.Any devices wired to the
relayswillbecomeactiveduringsimulationmode.
1. InTOP‐LEVELMENU,selectHELP.
2. SelectSIM‐T.
3. Thedisplaywillstartat0.0.
a. Press and hold the UP button to begin
increasingthelevelofliquid.
b. Use the DOWN button to simulate the
loweringofliquidinthetank.
c. To increase speed, hold the SELECT button
whileholdtheUPorDOWNkeys.
4. Test the functionality of the relays confirming
theirONandOFFlevels.
5. Toexit,pressandholdtheSELECTkey.
6. SelectEXITtoreturntoTOP‐LEVELMENU.
TestParameters:ThismoderunsdiagnosticteststhatconfirmoperationofEchoSwitch®.Thisisaproduction
testfeatureusedbythefactorytoconfirmoperation.
1. InTOP‐LEVELMENU,selectHELP.
2. SelectTEST
P.
3. TESTPwillperformthefollowingtest:
a. RunaLCDCheck
b. TurnONallthreerelays
c. TurnOFFallthreerelays.
4. TESTPwillalsolistthefollowingsettings:
5. SelectEXITtoreturntoTOP‐LEVELMENU.
Note:This mode should only be used when
supervisedbyaFlowlinerepresentative.