22of34 MN300282 RevA
CONFIGURATION(cont.) StepFive
Howto Time Alternate relays:Thisfunctionisonlyoperationalwhen two ormore relaysare configured as
pumps performing the same function (either filling or emptying).This function is useful when a complete
cycle of the pumps cannot be guaranteed such as a continuous inflowto a sump.Thus onepump may run
longer than the other pump.To insure equal wear ofboth pumps, the alternatingcycle can be set up ona
timer.Thustheleadandlagpumpswillbeswitchedbasedontimeratherthanacyclebasis.
1. Make sure at least two relays are in the same
mode.
a. Example: two relays are set as PUMPs that
FILL or three relays are set as PUMPs that
EMPTY).
b. If this condition is not met, M‐PLEX will not
appear.
2. InTOP‐LEVELMENUmode,selectM‐PLEX.
3. SelectDUPLEXorTRIPLX.
4. SelectA‐TIME.
5. SelectHOURS.
6. Using the UP and DOWN buttons, set the
AlternatingTimeinHours.
a. Alternating Time can be set from 0 to 600
hours.
7. To enter the value, press and hold SELECT for 2
secondsandrelease.SAVEDwilldisplay.
8. SelectEXITtoreturntoTOP‐LEVELMENU.