CONFIGURATION(cont.) StepFive
HowtoAlternatetworelays:AlternateenablesEchoSwitch®tousetworelaystoalternateaftereachcycle.
The configuration of Alternate is identical to Duplex with the exception of the Backup level is at a setting
wherethelevelwillneverachievesetpoint.Tobegin,configuretworelaysinthesamemode(ex:tworelays
aresetasPUMPsthatFILLortworelayssetasPUMPsthatEMPTY).BesuretosetonerelaywithanONSet
Pointat thePrimary Leveland theother relayON SetPoint atthe BackupLevel.Setting therelayswith the
sameONlevelwillhavecausebothrelaystoturnonatthesametime.TheBackuplevelmustbesettoalevel
outofrange(levelwillneverreachthissetting).Oncethisiscompleted,seethestepsbelow.Examplebelow
showstworelays(AandB)usedto
AutoEmptyatank:
1. Make sure at least two relays are in the same
modeforpumps.
a. If this is not true, then MPLEX will not
appear.
2. InTOPLEVELMENUmode,selectMPLEX.
3. SelectDUPLEX.
a. If three relays are configured in the same
mode,continuetostep4.
b. If only two relays are configured, jump to
step5.
4. Select R1_R2 (Relay 1 & 2), R2_R3 (Relay 2 & 3)
orR1_R3(Relay1&3).
a. EchoSwitch® will allow you to select two of
threerelaystoduplex.
5. Select
EXITtoreturntoTOPLEVELMENU.
